Smoke dilution and smoke extraction in Vienna and the surrounding area
In a fire, smoke is the greatest danger. AIRTEC designs, installs and maintains smoke dilution and smoke extraction systems for underground car parks, cellar storage compartments, airlocks and escape routes in Vienna and the surrounding area – coordinated with your stairwell pressurisation system on request.
Smoke dilution at a glance
In the event of a fire, a smoke dilution system (German: Brandrauchverdünnung, BRV) supplies fresh air and extracts the smoke-filled air. The smoke is diluted and removed so that escape routes remain usable and the fire brigade can find the source of the fire more quickly.
Applications: underground and multi-user car parks, storage rooms and cellar compartments, airlocks, escape routes, industrial buildings and warehouses
Design: mechanical with smoke extraction fans, or as natural smoke extraction via shafts and smoke control dampers
Control: our own tested AIRTEC DBA/BRV control cabinet with a touchscreen for the system status
Activation: via the fire alarm system or the system's own smoke detectors, or manually by the fire brigade at the fire brigade control panel
Service area: Vienna and surroundings – design, permit submission, installation, acceptance and maintenance from a single source
What is smoke dilution?
In the event of a fire, smoke dilution supplies large quantities of fresh air and extracts the smoke-filled air. This dilutes the smoke, keeps visibility and temperature bearable for longer, and helps the emergency services find the source of the fire more quickly.
Smoke extraction in the narrower sense removes the smoke from the fire area in a targeted way, for example via extraction points and jet fans. The right solution depends on the use, the floor plan and the fire safety concept – we coordinate this with your fire safety planner.
Natural smoke extraction with smoke control dampers
Not every smoke extraction system needs a fan. With natural smoke extraction, the hot smoke escapes outside through shafts or openings by its own buoyancy. In a fire, smoke control dampers open the way out – automatically via smoke detectors or the fire alarm system, or manually by the fire brigade; in normal operation, they keep the shaft closed. Whether natural smoke extraction is sufficient or mechanical smoke dilution is required depends on the building, its size and the fire safety concept – we design both. Typical applications are storage rooms and car parks. Compared with mechanical smoke dilution, however, natural smoke extraction requires considerably larger shafts – something that must be taken into account early in the building design.
Where we use smoke dilution
Underground and multi-user car parks
OIB Guideline 2.2 (Austrian building guideline on fire safety in car parks) requires smoke and heat exhaust systems for car parks with more than 250 m² of usable floor area. If natural smoke exhaust through openings is not possible, a mechanical system is used. Depending on the size and number of underground levels, further requirements apply, such as a fire alarm system. We design car park ventilation and smoke dilution together and, on request, install them with a shared control cabinet; dedicated smoke extraction fans are used in the event of a fire. Find out more about everyday ventilation under Car park ventilation & CO systems.
Storage rooms and cellar compartments
Cellar compartments in residential complexes are often windowless, located on underground levels and full of combustible material. Where the fire safety concept requires smoke removal and natural openings are not possible, mechanical smoke dilution ensures that the smoke does not spread into corridors and stairwells.
Airlocks
Airlocks between the car park, cellar and stairwell keep smoke away from the escape route. We equip them with smoke dilution or airlock ventilation and coordinate them with the adjoining systems.
Working together with the stairwell pressurisation system
A stairwell pressurisation system keeps the stairwell free of smoke by means of positive pressure, while smoke dilution removes the smoke from the adjoining areas. For both to work together, air volumes, air release and controls must be matched to each other – which is why we design smoke dilution and pressurisation from a single source. Find out more about the stairwell pressurisation system.
Escape routes and special solutions
We have also designed and implemented smoke dilution for special situations, such as an escape route leading from the stairwell to the outside. Get in touch if your fire safety concept calls for a bespoke solution.
Industrial buildings and warehouses
We also design and install smoke dilution and smoke extraction systems in warehouses, commercial kitchens, bakeries and other industrial buildings – tailored to the use, the fire compartments and the fire safety concept. Find out more about our services for businesses under Commercial & industrial.
How smoke dilution works in a fire
All components of our smoke dilution systems
Which components a system needs depends on the building, its use and the fire safety concept. Here you will find all the components we use – one click takes you to the description.
- Control cabinet & activation
Our own development, triggered by the fire alarm system, smoke detectors or the fire brigade
- Status display with touchscreen
System status and precise fault messages at a glance
- Fire brigade control panel
Simple with a key switch or extended with a touchscreen
- Smoke extraction fans
Extract smoke even at high temperatures
- Smoke control dampers
Control the smoke zones
- Fire dampers
Keep fire compartments sealed
- Jet fans
Impulse ventilation for large car parks
- Replacement air
Fresh air via entrances, shafts or supply air
Control cabinet of our own development and activation
The heart of every system is our own tested control cabinet of the AIRTEC DBA/BRV type, which we also use for our stairwell pressurisation systems. It controls fans and dampers and can be operated manually by the fire brigade.
The system is triggered via the building's fire alarm system or via the system's own smoke detectors. On request, car park ventilation and smoke dilution can be combined in a shared control cabinet. Because we developed it ourselves, we know every function – during design, acceptance and maintenance.
Smoke extraction fans
Smoke extraction fans draw off the smoke-filled air and discharge it outside. They keep running reliably even at high flue gas temperatures. In car parks, we use dedicated smoke extraction fans for the event of a fire, separate from the fans of the everyday ventilation.
Status display with touchscreen
Since 2026, every one of our systems has been fitted with a touchscreen in the distribution board. Using their access code, the fire safety officer can see the current system status at any time – and, in the event of a fault, exactly what it is. This makes self-inspections easier and saves time when there is a fault, because it is clear from the very first call what the problem is.
Fire brigade control panel
The fire brigade operates the system manually via the fire brigade control panel. We build it in two versions:
Simple control panel: a key switch enables operation and switches between auto, off and manual. It can also be used to acknowledge an activation by a manual call point or smoke detector and to reset the system. The warning horn can be acknowledged even without enabling operation.
Extended control panel with touchscreen: in addition, the fire brigade can use the touchscreen to control individual dampers, fans and the entire system – for example to extract smoke from one specific area only.
Smoke control dampers
Smoke control dampers determine from which area the smoke is removed. In normal operation they are closed; in a fire, they open automatically via smoke detectors or the fire alarm system, or manually by the fire brigade. With natural smoke extraction, they open the shaft through which the smoke escapes outside by its own buoyancy.
Fire dampers
Where ventilation ducts pass through walls or ceilings between fire compartments, fire dampers close the duct in the event of a fire. This prevents fire and smoke from spreading into other fire compartments via the ductwork.
Jet fans (impulse ventilation)
In large or irregularly shaped car parks, jet fans mounted below the ceiling push the smoke towards the extraction points. This means the system does not need a continuous duct network.
Replacement air (supply air)
Air can only be extracted if fresh air flows in. Depending on the building, the supply air flows in via entrances and ramps or shafts, or is introduced mechanically. We size the replacement air to match the volume of air extracted.
Our complete package
Design in line with the OIB guidelines and the relevant ÖNORM standards (Austrian standards; for car parks, among others, ÖNORM H 6029), coordinated with the fire safety planner and architect.
Permit submission to the building authority – in Vienna, MA 37 (the municipal building authority).
Installation of fans, ducts, dampers and controls.
Commissioning, functional testing and acceptance by an accredited inspection body.
Periodic inspection and maintenance, so that the system works reliably in an emergency.
Service area: Vienna and surroundings
We install smoke dilution systems throughout Vienna as well as in Mödling, Baden, Klosterneuburg, Schwechat, Tulln, Korneuburg and the entire wider Vienna area. We are familiar with the requirements of the Vienna building authority from numerous projects. You can report faults of safety systems around the clock on +43 1 804 05 71 – outside office hours via our automated fault reporting service.
Frequently asked questions about smoke dilution
What is the difference between smoke dilution and stairwell pressurisation?
Smoke dilution removes smoke from the affected area, for example from the car park or cellar. Pressurisation keeps the stairwell free of smoke by means of positive pressure. In many buildings, the two work together.
How is a smoke dilution system triggered?
Via the building's fire alarm system or via the system's own smoke detectors. In addition, the fire brigade can trigger and operate the system manually at the fire brigade control panel.
How can I tell whether the system is in working order?
Since 2026, a touchscreen in the distribution board of our systems has shown the current system status. Using their access code, the fire safety officer can also see there exactly which fault has occurred.
From what size does a car park need smoke and heat exhaust?
Under OIB Guideline 2.2, smoke and heat exhaust systems are required for car parks with more than 250 m² of usable floor area. The exact design depends on the fire safety concept.
What air change rate is required in a car park?
That depends on the size of the car park and the federal province. In Vienna, according to MA 37, a 12-fold hourly air change, based on a room height of 3 m, is sufficient for car parks up to 500 m². For larger car parks, we calculate the required capacity individually.
Do cellar compartments need smoke dilution?
That is determined by the fire safety concept and the building permit. We review your documents and propose a suitable solution.
Does every smoke extraction system need a fan?
No. With natural smoke extraction, the smoke escapes by its own buoyancy through shafts that smoke control dampers open in the event of a fire. The fire safety concept determines which solution is suitable.
What is the difference between a smoke control damper and a fire damper?
A smoke control damper opens in a fire so that smoke can be removed in a targeted way. A fire damper closes in a fire so that fire and smoke cannot spread into other fire compartments via ventilation ducts.
Can car park ventilation and smoke dilution be combined?
Yes. We design both systems together and, on request, install them with a shared control cabinet. The fans are separate, however: dedicated smoke extraction fans are used in the event of a fire.
Who accepts the system?
An accredited inspection body tests and confirms that the system works once it has been completed. We attend this appointment and provide all the documents.

Discuss your project now
Planning a building project or received a fire safety requirement? Call us on +43 1 804 05 71 – we review your documents and draw up a tailored concept for you.