In a fire, the stairwell has to stay free of smoke – as an escape route for residents and as an access route for the fire brigade. AIRTEC designs, installs and maintains stairwell pressurisation systems in Vienna and the surrounding area, tailored to your building's fire safety strategy.

Stairwell pressurisation at a glance

In the event of a fire, a stairwell pressurisation system (in Austria: Druckbelüftungsanlage, DBA) builds up overpressure in the stairwell so that smoke cannot get in. This keeps the stairwell usable as an escape route for residents and as an access route for the fire brigade. In Austria, design, installation, testing and operation are governed by TRVB 112 S (Austrian technical guideline for fire protection).

  • Where: stairwells and, where required, lobbies, corridors and lift shafts

  • Concepts: stay-in-place concept, evacuation alarm concept or firefighting concept – depending on the building

  • Control: our own tested AIRTEC DBA/BRV control cabinet with a touchscreen showing the system status

  • Activation: automatically via smoke detectors or the fire alarm system, manually via manual call points or the fire brigade control panel

  • Testing: routine self-inspections by the operator, annual maintenance and an inspection by an accredited inspection body at least every two years

  • Service area: Vienna and the surrounding area – design, installation, acceptance and maintenance from a single source

How a stairwell pressurisation system works

The pressurisation system builds up overpressure in the stairwell – and, where required, in lobbies, corridors and lift shafts. This prevents smoke and other toxic gases from entering: through every open door, air flows from the stairwell towards the fire, not the other way round.

At the same time, the stairwell is flushed from bottom to top with at least 15,000 m³ of fresh air per hour, so any smoke that does get in is carried back out. People can escape via the stairwell, and the fire brigade can use it as an access route for firefighting.

Designed around your fire safety strategy

Which pressurisation concept a building needs is set out in its fire safety strategy or by the authorities. This determines how powerful the system has to be, whether a fire alarm system is required and whether the lift shafts are included.

We design every system to the current TRVB 112 S and coordinate it with the fire safety engineer, the fire alarm contractor, the lift company and the authorities. The overpressure is always limited so that every door can be opened with a force of no more than 100 N.

Which concept suits your building?

TRVB 112 S distinguishes between three main concepts for stairwells. They differ in how many people escape, how long the stairwell must stay smoke-free and how strong the airflow through open doors has to be.

Stay-in-place concept

Evacuation alarm concept

Firefighting concept

Typical buildings

residential buildings with an escape level up to 32 m, small-scale offices up to 22 m

larger offices, hotels, smaller event venues up to 32 m

high-rise buildings over 32 m, hospitals, shopping centres, places of assembly

Who escapes?

only those directly affected; everyone else stays in their flat

everyone on the affected floor

many people; evacuation takes longer

Smoke-free during

the escape

the evacuation

the entire firefighting operation

Airflow through open door

at least 1 m/s

at least 1 m/s, even with the exit door open

at least 2 m/s, even with a fire hose in the doorway

Fire alarm system

not mandatory; smoke detectors are sufficient

required

required

Lift shafts

firefighting lift is pressurised as well

firefighting lift is pressurised as well

firefighting and passenger lifts are pressurised as well

Pictogram

A

R

B

  • Stay-in-place concept

    For residential buildings: those affected escape – everyone else stays safely in their flat.

  • Evacuation alarm concept

    For offices and hotels: the fire alarm system raises the alarm and the floor is evacuated.

  • Firefighting concept

    For high-rise buildings and hospitals: smoke-free throughout the entire fire brigade operation.

TRVB 112 S also covers the room protection concept for individual rooms, such as refuge rooms for people with reduced mobility or security control centres, and the escape corridor concept for pressurised escape corridors. The concepts can also be combined. Basis: TRVB 112 S, 2026 edition.

What happens when the system is activated

  1. Step 1

    Fire detected

    A smoke detector in the stairwell or the fire alarm system detects smoke. Alternatively, residents activate the system manually via a manual call point, or the fire brigade does so at the fire brigade control panel.

  2. Step 2

    Doors and lifts

    Doors to the stairwell that are held open close. The lifts travel to the exit level and remain there with their doors open.

  3. Step 3

    Supply air

    The control cabinet opens the louvre dampers at the fan and starts the supply air fan, which delivers fresh air into the stairwell – and, depending on the concept, into the lift shafts. On the fire floor, the air release opening opens.

  4. Step 4

    Overpressure control

    The differential pressure sensor continuously measures the pressure in the stairwell relative to the outside. The pressure relief keeps the overpressure constant – high enough to keep smoke out, low enough for the doors to still be opened.

  5. Step 5

    Fire brigade takes over

    At the fire brigade control panel, the fire brigade switches to manual mode using the key switch. On the extended control panel with touchscreen, they can control dampers and fans individually. Their commands take priority over the automatic system.

All components of our stairwell pressurisation systems

A pressurisation system is much more than a fan. Here you can see every component we use, depending on the building and its fire safety strategy – click to jump to the description.

Control cabinet – our own development

At the heart of the system is our own tested AIRTEC DBA/BRV control cabinet, which we also use for our smoke dilution systems. It controls the entire system: the supply air fan, which delivers the required volume of air into the stairwell, and the electric pressure relief damper, which keeps the pressure constant. It also controls the air release dampers, the fire mode of the lifts and the holding magnets of the corridor doors.

The system is activated automatically via its own smoke detectors or a fire alarm system, and manually via manual call points or the fire brigade control panel. The cabinet forwards activations and faults to the person responsible for the system. Because we developed the control cabinet ourselves, we know every function inside out – during design, acceptance and maintenance.

Touchscreen status display

Since 2026, every one of our systems has a touchscreen in the distribution board. Using an access code, the fire safety officer can check the current system status at any time – and, in the event of a fault, see exactly what it is. This makes self-inspections easier and saves time when a fault occurs, because it is clear from the very first call what the problem is.

Supply air fan

The supply air fan delivers the required volume of air into the stairwell. It can be installed close to the ground on the ground floor, on the façade or on the roof. We use medium-pressure axial fans from Systemair's AXC series, with a galvanised steel casing and an aluminium hub and blades.

Fast-acting louvre dampers at the fan

Fast-opening louvre dampers are fitted in front of the supply air fan. In normal operation they are closed, preventing draughts in the stairwell and keeping the cold out in winter. When the system is activated, they open immediately so that the fan can deliver supply air without obstruction.

Pressure relief

The pressure relief regulates the overpressure. It adjusts the free cross-section so that the pressure in the stairwell remains constant, and always stays partly open during operation so that the stairwell is continuously flushed. It is designed either as a rooflight on the top floor – which, in the stay-in-place concept, also serves as the chimney sweep's roof access – or as a window or motorised louvre damper in the wall of the top floor.

Air release dampers (BRSK)

To allow the supplied air to escape in a controlled way, we use smoke control dampers (Brandrauchsteuerklappen, BRSK) as air release dampers. They open automatically when the system is activated – but only on the fire floor. At the extended fire brigade control panel, the fire brigade can override them and choose the air release on a specific floor, depending on the situation.

Basic fire brigade control panel during a lamp test

Fire brigade control panel (FBF)

The fire brigade control panel is located where the fire brigade enters the stairwell. Its commands take priority over the automatic system. We build it in two versions:

  • Basic control panel: a key switch enables operation and switches between Auto, Off and Manual. It can also be used to acknowledge an activation by a manual call point or smoke detector and to reset the system. The alarm horn can be acknowledged even without enabling operation.

  • Extended control panel with touchscreen: in addition, the fire brigade can use the touchscreen to control individual dampers, fans and the entire system – for example to select the air release on a particular floor, as is often required in the evacuation alarm and firefighting concepts.

Manual call points (DKM)

Anyone who notices a fire can activate the pressurisation system manually using a manual call point. The orange call points are clearly visible at the stairwell exit and on the top landing. A single press switches the system to flushing mode and closes any doors held open. LEDs show the system status, and a reset button resets it after a false alarm – but never while the fire alarm system is in alarm.

Smoke detectors and fire alarm system

Optical smoke detectors at the highest point of the stairwell and on the landings leading to flats or corridors activate the system automatically. If the building has a fire alarm system, it activates the pressurisation system directly. Without a fire alarm system, stairwell pressurisation is only permitted under the stay-in-place concept.

Differential pressure sensor

The differential pressure sensor continuously measures the pressure difference between the stairwell and the outside. The control cabinet uses this reading to regulate the pressure in the stairwell.

Key switch for roof access and ventilation

A key switch allows the opening on the top floor to be opened in everyday use too – as access to the roof or to air the stairwell. On request, we integrate a wind and rain sensor so that the opening does not stay open in storms or rain.

Door holding magnets and free-swing door closers

Corridor doors that are meant to stay open in everyday use are held by holding magnets; free-swing door closers allow them to be opened easily. When the system is activated, the control cabinet releases them all at once: the doors close and separate the corridor from the stairwell.

Lifts: fire mode control

When the system is activated, the lifts travel to the exit level and remain there with their doors open. This means nobody can get in any more, and no lift is left standing on a smoke-filled floor.

Pressurisation of lift shafts

Lift shafts connect every floor and could spread smoke throughout the building. The shaft of a firefighting lift is therefore always pressurised as well – with at least 5 Pa more pressure than the stairwell, with doors open as well as closed. In the firefighting concept, and generally with an escape level above 32 m, the shafts of passenger lifts are included too and are kept at least at the same pressure as the stairwell.

Stairwell pressurisation and smoke dilution

A pressurisation system often works together with a smoke dilution system in the car park, basement or lobby: the pressurisation system keeps the stairwell free of smoke, while the smoke dilution system removes smoke from the adjoining areas. To make sure the two do not interfere with each other, we design them together from a single source.

Our scope of services

  1. Design and planning of the system to TRVB 112 S

  2. Supply and installation of all components

  3. Commissioning and acceptance by an accredited inspection body

  4. Periodic testing and maintenance

Service area: Vienna and surroundings

We install stairwell pressurisation systems throughout Vienna as well as in Mödling, Baden, Klosterneuburg, Schwechat, Tulln, Korneuburg and the wider Vienna area. Faults in safety systems can be reported around the clock on +43 1 804 05 71 – outside office hours via our automated fault reporting service.

FAQ on stairwell pressurisation

When is a stairwell pressurisation system required?

Mainly in taller buildings and where the stairwell cannot be kept smoke-free in any other way. The exact requirements are set out in the fire safety strategy or by the authorities.

What pressurisation concepts are there?

For stairwells, TRVB 112 S distinguishes between the stay-in-place concept (e.g. residential buildings), the evacuation alarm concept (e.g. offices, hotels) and the firefighting concept (e.g. high-rise buildings, hospitals). In addition, there are the room protection and escape corridor concepts.

How is a stairwell pressurisation system activated?

Automatically via smoke detectors in the stairwell or the building's fire alarm system, manually via manual call points, or by the fire brigade at the fire brigade control panel.

What happens when the system is activated?

Doors held open close, the lifts travel to the exit level, the louvre dampers open and the supply air fan starts. The pressure relief regulates the overpressure, and the air release opening on the fire floor opens.

How can I tell whether the system is working properly?

Since 2026, a touchscreen in the distribution board of our systems shows the current system status. Using an access code, the fire safety officer can also see exactly which fault has occurred. In addition, LEDs on the manual call points and the fire brigade control panel show whether the system is ready for operation, faulty or activated.

Are lifts pressurised too?

Yes. The shaft of a firefighting lift is always pressurised as well, with at least 5 Pa more pressure than the stairwell. In the firefighting concept, and with an escape level above 32 m, the shafts of passenger lifts are included too.

Is there a draught from the fan into the stairwell?

No. In normal operation, fast-acting louvre dampers close the opening at the fan – keeping out draughts and cold air. They only open when the system is activated.

Can the system also be used to air the stairwell?

Yes, a key switch allows the opening on the top floor to be opened in everyday use, for example for ventilation or as roof access. A wind and rain sensor can also be integrated.

What is the difference from smoke dilution?

Stairwell pressurisation keeps the stairwell smoke-free by means of overpressure, while smoke dilution removes smoke from the car park, basement or lobby.

Who carries out the acceptance inspection?

After completion, an accredited inspection body checks the system's function, including pressure, airflow and door opening force measurements. We attend the inspection and provide all documentation.

How often does a stairwell pressurisation system have to be inspected?

The operator or the person responsible for the system carries out regular self-inspections – under TRVB 112 S, quarterly for fans, pressure control, air release openings and signals, while the stairwell is checked monthly to make sure it is kept clear. The system is serviced once a year, and at least every two years an accredited inspection body inspects it as part of a periodic inspection.

Branched galvanised steel ventilation ducts with round pipes and bends, fans of a ventilation system in the background