Pressurisation system on a flat roof with galvanised ducts and two tubular fans, city view in the background

Stairwell pressurisation: the evacuation alarm concept

The concept for offices, hotels and event venues: the fire alarm system raises the alarm early, the affected floor is evacuated – and the stairwell stays smoke-free throughout.

The evacuation alarm concept at a glance

Under the evacuation alarm concept (Räumungsalarmkonzept) of TRVB 112 S (Austrian technical guideline for fire protection), everyone on the affected floor or in the affected fire compartment leaves the building in the event of a fire. A fire alarm system detects the fire early and raises the alarm. The stairwell pressurisation system keeps the stairwell smoke-free while the evacuation is under way – in other words, during the phase in which the fire is still at an early stage.

  • Typical buildings: larger office buildings, larger accommodation establishments and smaller event venues with stewards – each with an escape level of up to 32 m

  • Requirements: a fire alarm system (at least fire compartment protection) and an alarm organisation with floor-by-floor evacuation

  • Principle: at least 30 Pa overpressure with doors closed; if the door on the fire floor and the exit door are open, air flows towards the fire area at a speed of at least 1 m/s

  • Marking: pictogram “R” at the fire brigade access to the stairwell

The principle in simple terms

In an office building, many people work on each floor and cannot retreat to a safe flat. If a fire breaks out on the fifth floor, the fire alarm system will usually report it before it has fully developed. The affected floor is evacuated and everyone leaves via the stairwell.

During this time, the doors on the fire floor and at the exit at the bottom are open. The pressurisation system blows so much fresh air into the stairwell that it flows towards the fire area at a speed of at least 1 m/s, even through these open doors. Small amounts of still cool smoke that do get into the stairwell during the escape are flushed back out by the system.

For this to work, the people in the building need to know what to do when the alarm sounds: they know their escape route and practise the evacuation regularly – or trained staff assist them.

What happens in a fire

  1. Step 1

    Fire alarm system raises the alarm

    An automatic fire detector is triggered. The fire alarm system raises the evacuation alarm for the affected floor or fire compartment and starts the pressurisation system. A manual call point of the fire alarm system, on the other hand, does not start it.

  2. Step 2

    Doors, lifts, air release

    Doors to the stairwell that are held open close, and the lifts travel to the exit level and remain there with their doors open. On the fire floor, the air release opening opens automatically or an air release system starts – only there and nowhere else.

  3. Step 3

    Evacuation via the stairwell

    People leave the floor. The overpressure and the airflow through the open doors keep the stairwell smoke-free. If there is a lobby in front of the stairwell, it is flushed with fresh air at least 30 times per hour.

  4. Step 4

    Fire brigade takes over

    At the fire brigade control panel, the fire brigade controls the system manually and – if there are no windows on the floor that can be opened from outside – can select the air release on a specific floor.

What the building needs

  • A fire alarm system to TRVB 123 S (Austrian guideline for fire alarm systems), with at least fire compartment protection for the areas along the escape route

  • An alarm organisation with evacuation by floor or fire compartment, occupants who know the building and hold evacuation drills, or assisting staff

  • Self-closing doors to the stairwell and at the exit; free-swing door closers all close together in a fire

  • Automatically opening air release openings or an air release system on each floor

  • Lifts with fire mode control; the shaft of a firefighting lift is pressurised as well, with at least 5 Pa more pressure than the stairwell

Where the limits lie

The evacuation alarm concept is designed for the evacuation phase, while the fire is still at an early stage. If the fire brigade later has to keep a door permanently open for a fire hose, it can no longer reliably keep the stairwell free of smoke. That is what the firefighting concept is for.

In residential buildings, where residents can stay in their flats in the event of a fire, the stay-in-place concept is usually sufficient.

What operators should keep in mind

  • Put the alarm organisation into practice: evacuation drills and briefing new employees are part of the concept.

  • Do not hold doors open: wedges or furniture at stairwell doors render the system ineffective.

  • Self-inspections: every quarter, fans, pressure control, air release openings (as random checks, all within five years) as well as alarm and fault forwarding.

  • Maintenance and inspection: annual maintenance and an inspection by an accredited inspection body at least every two years – we take care of the maintenance.

  • Coordinate alterations: clarify changes to the stairwell or to the room layout between the stairwell and the air release opening with the inspection body beforehand.

FAQ on the evacuation alarm concept

What is the difference from the stay-in-place concept?

Under the stay-in-place concept, most people stay in their flats and only one door is open. Under the evacuation alarm concept, everyone on the affected floor leaves the building and several doors are open – so the system must maintain an airflow of at least 1 m/s even through open doors and requires a fire alarm system.

Which buildings is the evacuation alarm concept intended for?

Under TRVB 112 S, for example larger office buildings, larger accommodation establishments and smaller event venues with stewards, each with an escape level of up to 32 m. What applies to your building is set out in the fire safety strategy.

Is it possible without a fire alarm system?

No. Early alarm by a fire alarm system is the basis of the concept: only then is the evacuation complete before the fire has fully developed.

Does smoke get into the stairwell during the evacuation?

Small amounts of still cool smoke can briefly enter while doors are open. The system continuously flushes the stairwell from bottom to top with at least 15,000 m³ of fresh air per hour and removes this smoke again.

What happens to the lifts?

In a fire, they travel to the exit level and remain there with their doors open. The shaft of a firefighting lift is pressurised as well, with at least 5 Pa more pressure than the stairwell.

Branched galvanised steel ventilation ducts with round pipes and bends, fans of a ventilation system in the background

Pressurisation for your office or hotel building?

We design stairwell pressurisation systems to TRVB 112 S and coordinate them with the fire alarm system and the fire safety engineer. Call us on +43 1 804 05 71.