Stairwell pressurisation: the firefighting concept
The concept for high-rise buildings, hospitals and large buildings: the stairwell stays smoke-free throughout the entire firefighting operation – even when the fire brigade holds doors open for its fire hose.
The firefighting concept at a glance
The firefighting concept (Brandbekämpfungskonzept) is the most demanding concept for stairwell pressurisation systems under TRVB 112 S (Austrian technical guideline for fire protection). It is used where a very large number of people are present and evacuation takes longer. The system keeps the escape route and the fire brigade's access route smoke-free not only during the escape, but throughout the entire firefighting operation.
Typical buildings: high-rise buildings with an escape level above 32 m, larger places of assembly, shopping centres and department stores, large hotels, hospitals
Principle: even with several doors open – including the door through which the fire hose runs – air flows from the stairwell towards the fire at a speed of at least 2 m/s
Lifts: the firefighting lift and the regular passenger lifts are included in the pressurisation
Marking: pictogram “B” at the fire brigade access to the stairwell
The principle in simple terms
In a high-rise building or hospital, the fire brigade is often on site for a long time. By the time it arrives, the fire floor is usually already heavily smoke-logged. Firefighters take the firefighting lift to the floor below the fire, connect their fire hose there and carry it up the stairwell to the fire floor.
During this time, many doors are open at once: the stairwell door and the door to the fire area on the fire floor, the doors on the floor below through which the hose runs, the lift doors and the exit door at the bottom. Even so, no smoke may enter the stairwell – it is the route used by the emergency services and by many people who are still escaping.
This is why the concept assumes a fire that has already developed and requires twice the air velocity of the other concepts: at least 2 m/s through the open stairwell door. This calls for considerably larger fans and shafts, and careful coordination with the fire alarm system, the lifts and the fire brigade.
What happens in a fire
Firefighting lift and passenger lifts
Lift shafts connect every floor – without countermeasures, they would spread smoke throughout the building. That is why the following applies:
Firefighting lift: its shaft is pressurised in every pressurisation system and is always at least 5 Pa above the pressure in the stairwell – with doors open as well as closed.
Passenger lifts: in the firefighting concept – and generally with an escape level above 32 m – the shafts of regular lifts whose doors open into the pressurised area are included too. They are kept at least at the same pressure as the stairwell.
What the building needs
A fire alarm system that activates the pressurisation system
Supply air, shafts and fans that maintain the airflow even with many doors open
Pressure control so that every door can still be opened with a force of no more than 100 N
Air release openings or air release systems on each floor that open only on the fire floor
Wall hydrants within the occupied areas; additional hose connections in lobbies or the stairwell, or a sprinkler system, can reduce the requirements for open doors
A fire brigade control panel at the fire brigade's point of attack
Early planning pays off
A firefighting concept affects shafts, plant areas, doors and lifts. The earlier we are involved in the planning, the easier it is to accommodate air paths and fans. We coordinate the system with the fire safety engineer, the fire alarm contractor, the lift company and the inspection body, and attend the acceptance inspection by the accredited inspection body.
Lower requirements apply to the stay-in-place concept for residential buildings and the evacuation alarm concept for offices and hotels.
FAQ on the firefighting concept
When is a firefighting concept required?
When a building is intended for many people and evacuation takes longer – under TRVB 112 S, for example, in high-rise buildings with an escape level above 32 m, larger places of assembly, shopping centres, department stores, large hotels and hospitals. It is specified in the fire safety strategy or in the official approval procedure.
Why do the passenger lifts have to be pressurised too?
Because lift shafts run through every floor. If they are not pressurised, smoke can travel via the shaft to other floors and into the protected area. In the firefighting concept, they are therefore kept at least at the same pressure as the stairwell.
What is the difference from the evacuation alarm concept?
The evacuation alarm concept protects the stairwell during the evacuation while the fire is still at an early stage (at least 1 m/s). The firefighting concept keeps it smoke-free throughout the entire firefighting operation, even with doors open for the fire hose (at least 2 m/s).
Can the stairwell door still be opened with so much pressure?
Yes. TRVB 112 S limits the door opening force to 100 N in every operating condition. The pressure control ensures that this value is not exceeded.
How often is the system inspected?
The operator carries out quarterly self-inspections, the system is serviced annually and inspected by an accredited inspection body at least every two years. We take care of the maintenance.

Major project with a firefighting concept?
The earlier we are involved, the better the pressurisation system can be integrated into the building. Call us on +43 1 804 05 71.